Page 17 - Bosch Boiler House Component
P. 17

Boiler house components | 17






          Water analyzer WA


          Reliable boiler operation is dependent on good water    For sample preparation, flow coolers for boiler water
          quality. The water analyzer continuously measures and     and boiler feed water, as well as control valves for
          monitors:                                               switching and distributing each individual medium
           pH value of the boiler water                         Flow rate indicator for visual inspection
           pH value, oxygen content and conductivity of the
            boiler feed water                                   The electronic component consists of:
           pH value and conductivity of the condensate or       Control unit including touch panel
            steam accumulator water content                      Power supply
                                                                 Electronics for the measuring modules
          All data is transmitted to the system control SCO via    Communication processors for data exchange
          the bus system. This means that all the key water       between the water analyzer WA and system
          parameters, including the conductivity of the boiler     control SCO
          water and that of the individual condensate flows, are
          therefore available in the system control SCO.        Benefits at a glance:
          Demand-based control and monitoring tasks can be       Increase in operating safety thanks to continuous
          performed fully automatically. If specified limit values     monitoring of the water values
          are exceeded, all parameters are transferred to the    Automated monitoring with constant measurement
          fault message memory of the system control SCO.         of the pH value, oxygen content and conductivity
          Continuous logging of the data is also possible. The    Savings on chemicals thanks to needs-based dosing
          data can be transferred via the bus system to a higher-    of additives
          level control centre, where it can be further processed.    Increased system efficiency through reduced desalting
                                                                  losses and saving of exhaust vapour energy
          Functions of the water analyzer are:                   A water analyzer can monitor up to three boilers
           Infinitely variable control of the dosing system for     All the measured values can be transmitted via
            oxygen binding agents                                 Ethernet to the system control SCO or to the
           Infinitely variable control of the dosing system for      customer's control centre, where they can be fully
            alkalisation                                          visualized
           Control of the exhaust vapour valve incl. visualiza-
            tion of the exhaust vapour energy saved in kWh


          Construction
          The water analyzer consists of an analysis component
          and an electronic component, both of which are
          housed at the factory in two interconnected, wall-
          mounted casings.

          Equipment level
          The analysis component contains the measuring
          modules:
           pH control for measuring the pH value of the boiler
            feed water and of the boiler water content for a
            maximum of three boilers
           O 2 control for measuring the O 2 content of the
            boiler feed water
           Conductivity sensor for measuring the conductivity
            value of the boiler feed water