8 | Boiler house components



          Modules for steam boilers




          Our modules for steam boilers allow you to equip your system according to your
          requirements. They ensure maximum operating safety as well as long service life
          and a high level of efficiency under the specific operating conditions.




          Water service module WSM


          The water service module supplies steam boilers
          with degassed and chemically conditioned feed
          water and disposes of the desalting and waste water.


            Feed in and storage of condensate
            and make-up water
            Thermal partial deaeration of the feed water
            with WSM-T
            Thermal full deaeration of the feed water
            with WSM-V
            Chemical conditioning of the feed water
            Expansion and cooling of the desalting and
            waste water
            Cooling of the water samples
            PLC control and visualization of
            – water level in the tank
            – feed water temperature for the WSM-T             Water service module WSM-V for full deaeration for all steam
            – tank pressure for the WSM-V                      boilers with outputs ranging from 2,000 to approx. 100,000 kg/h.
            – blow-down temperature
            Control for chemical dosing
            Dry running protection feed pump module
            Overflow protection

          Construction
          All components are piped, thermally insulated and
          electrically wired into a multi-functional assembly unit.
          Complex scaffold constructions are not necessary: The
          compact module is mounted on a stable support device
          and designed for installing at ground level. All functions
          are computer-aided and automatically controlled with a
          programmable controller PLC with touch panel.












                                                                Water service module WSM-T for partial deaeration for all
                                                                steam boilers with outputs of up to 8,000 kg/h.
   3   4   5   6   7   8   9   10   11   12   13