10 | Boiler house components



          Condensate service module CSM
          Condensate high-pressure plant CHP


          Condensate from steam consumers is channeled,         mounted on a stable support device and designed for
          collected and temporarily stored in the condensate    installing at ground level. The condensate high-pressure
          service module. A condensate pump pumps the con-      plant is prepared for open installation and needs a
          densate back into the feed water deaeration plant if   positive suction head of at least 1.5 meters. All func-
          the corresponding need for water arises. Unpressur-   tions are computer-aided and automatically controlled
          ized condensate service modules are usually installed   with a programmable controller.
          near the consumer.
                                                                Equipment level
          With the condensate high-pressure plant the conden-   The system consists of the components condensate
          sate is kept at pressure and temperature so that expan-  tank, condensate pump module, control cabinet and
          sion steam losses are prevented or significantly redu-  equipment accessories. The system's piping and ther-
          ced. The condensate is fed directly to the steam      mal insulation is pre-installed ex works.
          boiler via the condensate pump when required.
          Deaeration once again of the high-pressure condensate   Benefits at a glance:
          is not necessary. Condensate high-pressure plants       Decrease in energy and water consumption
          should always be used if the discharge into the feed    by reducing make-up water quantities
          water tank or into unpressurized condensate service      Minimisation of expansion steam losses,
          modules would be accompanied by high expansion          desalting and blow-down quantities, less
          steam losses due to the condensate parameters.          chemical consumption and reduced corrosion
                                                                  potential in the steam condensate system when
          Construction                                            using condensate high-pressure plants
          All components are piped, thermally insulated and
          electrically wired into a multi-functional assembly unit.
          The unpressurized condensate service module is
































          The unpressurized condensate service module collects the   The amount of fuel, make-up water requirement and use of
          condensate streams and channels them back into the   chemical dosing agents for the water treatment can be reduced
          water/steam circuit via the deaeration system.       drastically by a condensate high-pressure plant.