Page 11 - Bosch Boiler House Component
P. 11

Boiler house components | 11



          Blow-down, expansion and                              Expansion and
          cooling module BEM                                    heat recovery module EHM


          The purpose of the blow-down, expansion and cooling   The module recovers a substantial amount of the heat
          module BEM is the intake of all hot waste water of a   quantity contained within the hot water (desalting
          steam boiler system. This waste water is collected, ex-   water/condensate) of a boiler system. In the expansion
          panded and cooled down to the permitted, set dis-     tank the water that is under pressure is expanded. The
          charge temperature. The module is designed for multi-  expansion steam produced thereby supports the heat-
          boiler systems with a max. of three steam boilers.    ing of the feed water tank. In the downstream heat
                                                                exchanger the make-up water of the boiler system is
          Construction                                          preheated and the desalting water/condensate is
          A closed, upright container mounted on a supporting   cooled to a temperature of approx. 35 °C.
          structure, with various feed and drain connections.
          The lower half of the module is filled with water during   Construction
          operation, the upper half is expansion space. The     The module comprises an expansion tank, an inte-
          prevailing media temperature is recorded and con-     grated heat exchanger for heat recovery, the support-
          verted to an electrical signal with the temperature   ing structure and the necessary equipment.
          measuring transducer in the lower part of the module.
          Mixed cooling is achieved by the supply of cold, sof-  Equipment level
          tened make-up water and the waste water is safely     The module is offered thermally insulated and fully
          drained off when the permitted discharge tempera-     assembled ex works with all necessary fittings.
          ture is reached. The discharge temperature can be
          controlled by the control system of the water service   Benefits at a glance:
          module.                                                 Quick and easy assembly, ready for immediate
                                                                  operation with few connections
          Equipment level                                         Increase in efficiency of the system
          The module comprises a vertical cylinder sealed with     Reduction of the fuel, cooling water
          plates at both ends and a protection against contact. It   and waste water costs
          is offered thermally insulated and fully assembled ex
          works with all necessary fittings.

          Benefits at a glance:
            Quick and easy assembly, ready for immediate
            operation with few connections
            Exact compliance with official guidelines thanks to
            automatic operating mode
   6   7   8   9   10   11   12   13   14   15   16